Project requirements
The BESS system is composed of two sets of one 0.5MW/1 MWH battery energy storage system, one sets of PCS, one set of EMS microgrid control system and one set of AC/DC distribution control system, environmental monitoring system, fire protection system, etc.
Battery System
Project |
Rated voltage |
Capacity |
Energy |
Group approach |
Battery cell |
3.2V |
280Ah |
0.896kWh |
/ |
Battery pack |
51.2V |
280Ah |
14.336kWh |
1P16S |
Battery cluster |
716.8V |
280Ah |
200.704kWh |
1P224S |
Battery system |
716.8V |
5*280Ah |
1003.52kWh |
5*1P224S |
1MWH LFP battery energy storage system configuration
Main equipment parameters and functions
Battery system
Cell Brand option: EVE/REPT/Great Power…
Battery module:280Ah 1P224S
Size (L*W*H) mm:D6058×W2896×H2438(±1)
Rated voltage:716.8V
Nominal capacity:280Ah
Nominal energy:1003.52kWh
Working voltage :604.8~806.4V
Maximum allowable operating temperature range
Charge:-20~45ºC;
Discharge:-20~45ºC
ESS extend warranty: 5years
DC combiner
The DC combiner cabinet integrates the battery management system control module (including human-machine interface), combiner circuit breaker, backup power UPS, etc., and plays a role in communication display of the entire battery system unit, battery cluster combiner, BMS emergency backup power, etc. Used for DC convergence of multiple battery clusters, reducing the number of cables connecting the battery system to PCS. 5 battery clusters are converged through one DC combiner cabinet and connected to the DC side of PCS
EMS energy management system
Self- developed EMS system, mastering core technology, customizable control strategies, cloud monitoring platform, 24-hour rapid response, worry free after-sales service.

PCS system
Rated power: 500kW
Rated voltage :AC 400V
Current rating :1125A
DC side voltage range:500-900VDC
Weight:2050KG
IP of Cabinet: IP20
Cooling method: Air cooling
Dimensions (W*H*D) 1400×1950×1000mm
Warranty: 5 years
BMS
The battery management system consists of a battery module management unit BMU, a battery cluster management unit BCMU, and current and temperature detection units. The BMS system has functions such as high-precision detection and reporting of analog signals, fault alarms, uploading and storage, battery protection, parameter settings, passive balancing, battery pack SOC calibration, and information exchange with other devices.
Cooling system
Battery container using air-cooled design, external industrial air-conditioning refrigeration heating system, through the container lithium battery thermal simulation effect of the container air duct design, to ensure that each way battery racks are able to meet the temperature balance, so that each group of battery racks of the upper and lower layers of the battery module temperature difference is controlled in the optimal operating temperature range.
Fire Protection System
Aerosol gas fire protection system with gas extinguishing control panel, detectors, manual alarm buttons, audible and visual alarms, alarm indicators.
20ft Container
C5 level, anticorrosion, with a certificate from the classification society, it can be transported by sea, Air cooling method conditioned.
Cables
DC side to AC side cables and AC and DC inside cables including Power cables, communication cables.